Shanghai DEMIKS Electric Power Technology Co.,LTD

Cable Fault Test System

demiks is a manufacturer of cable fault system equipment, to buy cable fault location system and know the price of cable fault system please contact us....


Product Details

Product Tags

Cable Fault Test System

Application:

Intelligent cable fault tester is our company in the power industry rapid progress opportunity, according to industry development and market demand, research and development and production of power cable fault test special system equipment.

It is mainly used for power cable open circuit, short circuit, ground, low resistance, high resistance flash-over and high resistance leakage fault test, as well as coaxial communication cable and local cable open circuit, short circuit fault test. It can also measure the speed of the wave, determine the length of the cable, etc., and can establish cable files for daily maintenance and management.

The product adopts the world's highest level of time domain reflectometry technology, fault waveform automatic distance judgment, simple and clear, easy to use; The whole machine adopts industrial control plastic chassis, small and delicate, easy to carry; The human-machine interface is friendly, even if non-professional personnel operate, you can still quickly get familiar with and use, efficient and accurate to complete the cable fault test.

 Features:

◆It is used for all kinds of faults of power cables of different grades, different sections, different media and various materials in 35kV and below.

Including: open circuit, short circuit, low resistance, high resistance leakage, high resistance flash-over fault.

◆Can cooperate with high-voltage equipment to realize the traditional cable fault test of low-voltage pulse method, impact flash-over method, speed measurement method (multiple pulse

pulse method optional).

◆All English operation software and user interface, sub-menu and text prompts to achieve human-machine interaction.

◆Industrial 10.4 inch color touch LCD display, all English operating software and user interface, submenu mode and text show human-machine interaction.

◆The global waveform and local waveform are displayed synchronously, which is convenient for overall analysis and detailed adjustment.

◆Built-in power supply, can be used for a long time in the environment without power supply.

◆Small size, light weight, easy to use, high failure detection success rate and test accuracy.

◆Stable performance in any environment, does not crash, signal acquisition high-voltage protection measures are safe.

◆Built-in storage/retrieval function, which can easily save or retrieve data and waveform for re-analysis.

◆The test signal provides a variety of pulse width, no test blind area.

Product Parameters:

1. Sampling method: low voltage pulse method, impact flashover method, speed measurement method (multiple pulse optional)

2. Sampling rate: 200 MHz, 100 MHz, 80 MHz, 40 MHz, 20MHz, 10 MHz

3.Pulse width: 0.05μs, 0.1μs, 0.2μs, 0.5μs, 1μs, 2μs, 8μs

4. Wave speed setting: cross-linked ethylene, polyvinyl chloride, oil-impregnated paper, non-dripping oil and unknown type self-setting

5. Impact high voltage: 35kV and below

6. Test distance: < 60km, blind area ≤1m

7. Resolution: 1m

8. Test accuracy: 1m

9. Display mode: Industrial grade 10.4 inch color touch LCD screen

10. Operation mode: touch screen operation, physical knob operation

11. Analysis Settings: scroll, zoom, save, call out, wave shift and other functions

12. Power supply: built-in battery power supply

13. Continuous operation: ≥8h (can also use external power supply), charging power AC220V±10%

14. Storage function: with data storage function, it can store a large number of field waveforms and data, and can be used at any time

15. Waveform analysis: All high-resistance fault waveforms are only represented as short-circuit fault waveform characteristics of low-voltage pulse method, which is easy to analyze

16. Waveform processing: The measured fault point waveform and the full-length open-circuit waveform of good phase can be displayed on the screen at the same time for the same screen

The fault distance can be determined automatically by comparison and superposition comparison